A ventilation study was performed on a Hydro Generator as part of an uprate study. The objective of the study was to determine if the existing ventilation would be sufficient to maintain satisfactory operating temperatures when the unit for a proposed uprate to 134 MVA from 82.5 MVA (62% increase).
Combining test measurements of stator vent velocities with EME equivalent resistance network modeling, a major stator vent air flow unbalance was discovered and corrected. Through the modeling, it was determined that the cause for the severe stator vent flow imbalance was instability of operating the rim mounted blowers in parallel and that the issue could be resolved by making which of the modifications identified below?
What would you do?
A.) Re-design rim fans
B.) Re-design rim fan shrouds
C.) Install baffles between the poles
D.) Modify end-turn vent restrictors